High Resistance Grounding

High Resistance Grounding (HRG) in Industrial Applications

High Resistance Grounding (HRG) is a method used to manage fault currents in electrical systems, particularly in industries such as chemical processing and oil & gas. It provides enhanced system reliability, personnel safety, and equipment protection by limiting ground fault currents. This post dives into the details of HRG, explaining its purpose, how it works, its benefits, and considerations for its use in industrial environments.


1. What Is High Resistance Grounding (HRG)?

High Resistance Grounding involves connecting the neutral point of a power system (e.g., transformer or generator) to the ground through a high-value resistor. This resistor limits the ground fault current to a manageable level, typically between 5 and 10 amps, which is enough to detect the fault but insufficient to cause significant damage or safety hazards.


2. Why Use HRG in Industrial Applications?

HRG is especially beneficial in industrial facilities like chemical plants and oil & gas facilities where operational continuity is critical and safety risks from electrical faults are high.

2.1 Common Challenges in Ungrounded or Low Resistance Systems

  • Ungrounded Systems:
    • While ungrounded systems allow continued operation during a fault, they pose risks of transient overvoltages and difficulty in fault detection.
  • Low Resistance Grounding:
    • Low resistance grounding allows higher fault currents, which may result in equipment damage and unnecessary system trips.

2.2 HRG Advantage

HRG offers a middle ground by enabling fault detection and controlled operation during a single fault without compromising system stability or safety.


3. How Does HRG Work?

3.1 System Configuration

  • A high resistance is connected between the system neutral and ground.
  • In systems without a neutral point (e.g., delta configurations), a zig-zag grounding transformer is used to create an artificial neutral.

3.2 Fault Management

  • When a ground fault occurs, the high resistor limits the fault current.
  • This small current allows:
    • Safe operation during a fault (typically for a limited time).
    • Detection and localization of the fault using monitoring devices.

3.3 Key Components of an HRG System

  1. Neutral-Ground Resistor (NGR): Limits the fault current to a safe value.
  2. Ground Fault Monitoring System: Continuously monitors ground current and alerts operators in case of faults.
  3. Zig-Zag Transformer (if needed): Creates a neutral point in delta systems.
  4. Alarm/Trip Circuit: Notifies personnel and may trip the system in case of prolonged faults or a second fault.

4. Benefits of HRG in Industrial Applications

BenefitDescription
Reduced Arc Flash HazardLimits fault current, reducing energy released during ground faults.
Operational ContinuityAllows the system to remain operational during a single ground fault.
Equipment ProtectionMinimizes damage to motors, transformers, and cables caused by high fault currents.
Enhanced Fault DetectionFacilitates easy identification and localization of ground faults.
Transient Overvoltage ControlPrevents transient overvoltages common in ungrounded systems.

5. HRG in Chemical and Oil & Gas Industries

5.1 Why HRG is Ideal for These Industries

  • Chemical Plants:
    • Continuous operations are critical to avoid shutdowns that could disrupt production or create safety risks.
    • HRG minimizes the risk of explosions caused by electrical sparks in hazardous areas.
  • Oil & Gas Facilities:
    • Flammable environments make limiting fault currents vital to reducing fire and explosion risks.
    • The ability to maintain system operation during faults enhances process safety and efficiency.

5.2 Common Applications

  • Motor Control Centers (MCCs): Protect motors from ground faults while maintaining operation.
  • Lighting Circuits: Prevent outages in essential lighting systems during faults.
  • Process Equipment: Avoid disruptions in critical systems like pumps and compressors.

6. Considerations for HRG Implementation

6.1 System Design

  • Determine the required resistance value based on system voltage and desired fault current.
  • Ensure proper sizing of the neutral grounding resistor to withstand fault conditions.

6.2 Fault Monitoring

  • Install reliable ground fault monitoring devices to detect and alert operators of faults promptly.

6.3 Maintenance

  • Periodically inspect and test the HRG system, including the resistor, monitoring devices, and connections.

6.4 Limitations

  • HRG systems cannot handle double faults (faults on two phases simultaneously), which may cause overcurrent and require a system trip.
  • Not suitable for systems where low fault currents could compromise protection device operation.

7. Comparison: HRG vs. Other Grounding Methods

FeatureHRGUngroundedLow Resistance Grounding
Fault CurrentLow (5–10 amps)Near zeroHigh
Transient OvervoltagesControlledHigh riskLow
System OperationContinues during single faultContinues during faultOften trips system
Equipment DamageMinimalIncreased riskHigher risk due to high currents
ApplicationsIndustrial processes, MCCs, hazardous areasSimple systems or legacy equipmentSystems requiring fast fault clearing

8. Practical Steps to Implement HRG

  1. Evaluate System Requirements:
    • Identify critical circuits where HRG can improve reliability and safety.
  2. Conduct a Fault Study:
    • Analyze system behavior under fault conditions to determine appropriate resistor sizing.
  3. Select Components:
    • Choose NGRs, monitoring devices, and transformers that meet the system’s voltage and current requirements.
  4. Install and Test:
    • Commission the HRG system with thorough testing to ensure functionality and fault detection.
  5. Train Personnel:
    • Educate operators and maintenance teams on how to respond to ground fault alarms and maintain the system.

9. Conclusion

High Resistance Grounding (HRG) is an invaluable tool for industries like chemical processing and oil & gas, where safety, reliability, and operational continuity are paramount. By limiting ground fault currents, HRG systems reduce the risks of equipment damage, arc flashes, and process disruptions, ensuring safe and efficient operations.

By carefully designing, implementing, and maintaining HRG systems, facilities can protect their assets, comply with safety regulations, and achieve long-term reliability in their electrical infrastructure.

Share The Post :