Direct on line starter

Around the world it famous with name DOL starter or direct on line starter.This is the most common starting method available on the market and at basic stater for all motor application.The starting equipment consists of only a main contactor and thermal or electronic overload relay.The disadvantage with DOL starter is that it gives the highest possible starting current.

A normal value is between 6 to 7 times the rated motor current but values of up to 9 or 10 times the rated current exist.Besides then DOL starter draw the starting current there also exists a current peak that can rise up to 14 times the rated current since the motor is not energized from the the first moment when starting.

What is DOL starter or Direct on line starter?

The values are dependent on the design and size of the motor, but in general, a smaller motor gives higher values than a larger one.

During a direct on line start, the starting torque is also very high, and is higher than necessary for most applications.The torque is the same as the force, and an unnecessary high force gives unnecessary high stresses on couplings and the driven application.

Naturally, there are cases where this starting method works perfectly and in some cases also the only starting method that works.

For more detail,please refer the MOTOR CONTROL HANDBOOK :-

Lemau: Lemau is Owner of Electricneutron.com .Involved in Electrical & Automation Engineering since 2001. Passionate to shared all experience & knowledge about Electrical.

View Comments (31)

    • Dear Yushar,use this formula to calculated the ampere,
      kW = I x V x 1.732
      I = 15kW / 415 x 1.732
      I = 20.86 @ 21
      MCB rating = 21 x 0.25 + 21 = 26.5 amp ( safety factor )

      u can used 40 ampere.it ok..no problem..u also can use 32 ampere of MCB.

      • sir if we use 40A and 32A mcb in the dol. so what is the meaning of breaking. and in the over load motor does not trip...that is wrong sir
        if i m wrong pls clearify
        i ask u apersonal question u r indian @admin

        • Miss priya in d o l starter there is a contactor, over load relay, start stop push button no NC and mccb. In over load relay we can set the current limit according to motor parameter. If motor overloaded due to any cause then over load relay tripped and circuit break. There is no concern of Mcb whether it is 40A or more. Mcb limit should be more than the motor, s current limit. I don't know it is satisfactory answer to you or not inform me.

    • Dear sir in 15 kw motor how can we use a DOL starter .it can be use only a star delta starter so is it a correct question?

      • DOL starter will generate high in rush current for big size motor.For better application, I suggest you to use VFD @ inverter.Easy to setup but quite expensive.Alternative you can use star delta starter.

  • What is the type of MCB (B,C,D etc) recommended in the above calculation?. What is the reference (book)used to select In+0.25xIn as the rating of MCB?. A MCB manufacturer says you should refer the tripping characteristics of MCB(type B,C,D) and make sure that for the starting current (say 6In)and duration of starting(say 4secs) the MCB will not trip. Does your formula satisfies this principle.

  • I'm young and fresh graduate of electrical engineering who wish to know more and promote techology inthe nworld.
    Please reply on how I can get a copy of this text-books

    • Hi mahdi,
      power factor is optional value for kW calculation,if have the power factor value,you can included in formula.also you can put efficiency value.So the answer more accurate :D that my 10 cent opinion...

      P = I x V x 1.73 x Pf x efficiency

    • if pf given then we use and where not given then assumed unity pf or approximately of respective

  • PLS SIR I WILL LIKE TO THE FIRST PERSON THAT INVENT OR INTRODUCE THE IDEA OF DIRECT-ON-LINE(DOL)STARTER, THE YEAR AND THE MONTH

  • Dear Sir,
    we can will be use 100hp motor in Dol Starter, This motor rating in safe of Dol Starter.

    Pls. reply

  • Dear Sir,
    we can will be use 100hp motor in Dol Starter, This motor rating in safe of Dol Starter of Hudraulic Powerpack ?

    Pls. reply